15-115 Pump Sense SetupThe Pump Sense function monitors pump on/off status to ensure that in-tank leak tests are not scheduled whenthe pumps are operating.Selecting the Pump Sense FunctionTo select Pump Sense Setup, press FUNCTION until you see the message:Press STEP to continue.Pump Sense ConfigurationIf necessary, press STEP until you see the message:Use this display to tell the system which Pump Sense module inputs are connected to pump controllers.NOTE: If Pump Sense modules are not installed, this function is not available.HOW THE SYSTEM CONFIGURES PUMP SENSE MODULESIf Pump Sense modules are installed, the system recognizes their presence and slot locations. The system alsoestablishes a module number based on the slot location. For example, if Pump Sense modules are installed in slots#10 and #13, the module in slot #10 automatically becomes module #1 and the module in slot #13 becomesmodule #2.As you specify which positions on a module are connected to which pumps, the system assigns a number, foreach pump, that corresponds to its position on the module. For example, if there is a pump connected to inputs 3and 4 of module 1, the pump connected to position 3 becomes S3 and the pump connected to position 4becomes S4.SPECIFYING PUMP SENSE POSITIONSIf position 1 is connected to a pump controller, press CHANGE and 1 appears (leave the X selection if no pumpinput is connected to position 1). Press the Right Arrow key to move to position 2. If a pump is connected to thisinput, press CHANGE and a 2 appears (leave X if there is no connection). Repeat these steps until you have all 4positions for the module selected. Press ENTER to confirm your selections. The system displays the followingmessage (in this example the first 3 positions are connected to pump controllers:Press STEP. If more than one module is installed, the system automatically advances to the PUMPSENS CONFIGmessage for the next module. Up to 8 modules may be installed. Repeat the steps described above for eachmodule until you have entered the configured all modules, and the system displays the SELECT TANK message.PUMP SENSOR SETUPPRESS TO CONTINUEPUMPSENS CONFIG: MODULE1SLOT # - X X X XSLOT # - 1 2 3 XPRESS TO CONTINUE