13 Volumetric Line Leak Tests Leak Test Start Time13-4To set the date of the weekly test, press CHANGE until the day on which you want to perform the test appears.Press ENTER to confirm the date:Press STEP to continue. The system displays the START TIME message. Follow the procedure under “Leak TestStart Time” on page 13-4.DAILY TESTTo run the tests daily, press CHANGE four times, then press ENTER in response to the ON DATE message:The system displays the message:Press STEP to continue. The system displays the START TIME message. Follow the procedure under below.Leak Test Start TimeIf necessary, press STEP until you see the message:You can enable the test by entering a start time or leave the test disabled.To leave the test disabled, press STEP. (The system displays the TEST RATE message.)To enter a test start time, press CHANGE in response to the START TIME message. Enter the start time and pressthe Right Arrow key to select AM or PM. Press ENTER to confirm your entry:NOTE: The system automatically establishes the correct test length.Press STEP to continue.Leak Test RateIf necessary, press STEP until you see the message:DAYPRESS TO CONTINUEALL LINES:ON DATETEST DAILY: ALL LINESPRESS TO CONTINUESTART TIME: ALL LINESTIME: DISABLEDTIME: XX:XX XMPRESS TO CONTINUETEST RATE: ALL LINES0.20 GAL/HR