5-155 System Setup Precision Test Duration (PLLD/WPLLD Only)Press STEP to display the message:This option allows either Tank Height or Tank Volume data for H-protocol. On power up, this feature will default toHEIGHT for backward compatibility. Press CHANGE, then ENTER to change the default. Accept the default if youare not using H-protocol.Precision Test Duration (PLLD/WPLLD Only)When optional 0.2 gph (0.76 lph) [PLLD and WPLLD] and 0.1 gph (0.38 lph) [PLLD only] line leak tests areenabled, this feature lets you extend the time between a passed test and running the next test from 12 hours (60hours with CSLD option), up to a maximum of 744 hours (31 days).Press STEP to display the message:Press CHANGE, then enter the desired duration (from 12 up to 744 hours without the CSLD option, or from 60up to 744 hours with the CSLD option), then press ENTER.Precision Line Test Auto-ConfirmThese Auto-Confirm selections reduce the risks of false 0.2 and 0.1 gph (0.76 and 0.38 lph) line test results.However, enabling these options extends the time it takes to post line test results.Press STEP to display the message:This feature evaluates several individual 0.2 gph line tests before a result is posted. To leave Auto-Confirmenabled, press STEP: To disable Auto-Confirm, press CHANGE, ENTER.Press STEP to display the message:This feature evaluates several individual 0.1 gph line tests before a result is posted. To leave Auto-Confirmenabled, press STEP: To disable Auto-Confirm, press CHANGE, ENTER.Press STEP to display the message:To leave the printing of 0.2 and 0.1 gph test results disabled, press STEP: To enable these printouts, pressCHANGE, ENTER.H-PROTOCOL DATA FORMATHEIGHTPRECISION TEST DURATIONHOURS: XXX0.2 GPH LINE TESTAUTO-CONFIRM: ENABLED0.1 GPH LINE TESTAUTO-CONFIRM: ENABLEDPRINT PRECISION LINETEST RESULTS: DISABLED