5-115 System Setup Line Annual Test Needed Warningsor conducted in a specified number of days (0 to 30), and activate an alarm if a test has not been passed after awarning, or a specified number of days.ENABLE LINE PERIODIC TEST NEEDED WARNINGS AND ALARMSTo enable Line Periodic Test Needed Warnings, press CHANGE, ENTER, then STEP. The system displays themessage:Press CHANGE, and enter the number of days (0 to 30 days) after which you want the system to warn that aperiodic line test has not been passed. Press ENTER. The system displays the message:Press STEP. The system displays the message:Press CHANGE, and enter the number of days (0 to 30) after which you want the system to alarm if a test has notbeen passed. This number should be higher than the number you set for the warning. Press ENTER. The systemdisplays the message:Press STEP. (The system displays the Line Annual Warnings message.)DISABLE LINE PERIODIC TEST NEEDED WARNINGSTo disable the line periodic warnings, press CHANGE in response to the Line Periodic Test Needed WarningsEnabled message. The system now displays:Press ENTER. The system confirms your choice with the message:Press STEP to continue. (The system displays the Line Annual Test Needed Warnings message.)Line Annual Test Needed WarningsIf necessary, press STEP until you see the message:LINE PER TST NEEDED WRNDAYS = XXXDAYS = XXXPRESS TO CONTINUELINE PER TST NEEDED ALMDAYS = XXXDAYS = XXPRESS TO CONTINUELINE PER TST NEEDED WRNDISABLEDDISABLEDPRESS TO CONTINUELINE ANN TST NEEDED WRNDISABLED