8.1.5 SettingsPID-6973-SETTINGS v3Table 93:OC4PTOC (51_67) Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/EnabledAngleRCA 40 - 65 Deg 1 55 Relay characteristic angle (RCA)AngleROA 40 - 89 Deg 1 80 Relay operation angle (ROA)NumPhSel 1 out of 32 out of 33 out of 3- - 1 out of 3 Number of phases required for phaseselection (1 of 3, 2 of 3, 3 of 3)DirModeSel1 DisabledNon-directionalForwardReverse- - Non-directional Directional mode of step 1 (Disabled, Nondir,Forward, Reverse)Characterist1 ANSI Ext. inv.ANSI Very inv.ANSI Norm. inv.ANSI Mod. inv.ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.IEC Def. TimeReservedProgrammableRI typeRD type- - ANSI Def. Time Selection of time delay curve type for step 1Pickup1 5 - 2500 %IB 1 1000 Operating phase current level for step 1 in %of IBaset1 0.000 - 60.000 s 0.001 0.000 Def time delay or add time delay for inversechar of step 1TD1 0.05 - 999.00 - 0.01 0.05 Time dial multiplier for the inverse time delayfor step 1IMin1 1 - 10000 %IB 1 100 Minimum operate current for step1 in % ofIBaset1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves forstep 1MultPU1 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for step 1DirModeSel2 DisabledNon-directionalForwardReverse- - Non-directional Directional mode of step 2 (Disabled, Nondir,Forward, Reverse)Table continues on next page1MRK 511 408-UUS A Section 8Current protectionPhasor measurement unit RES670 2.2 ANSI 173Technical manual