19.7.3.3 Function block GUID-C234101E-F9B9-4DB0-874C-C51BB50588CB v1IEC10000288-1-en.vsdI103MEASUSRBLOCK^INPUT1^INPUT2^INPUT3^INPUT4^INPUT5^INPUT6^INPUT7^INPUT8^INPUT9IEC10000288 V1 EN-USFigure 269: I103MEASUSR function block19.7.3.4 SignalsPID-3791-INPUTSIGNALS v5Table 507:I103MEASUSR Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of service value reportingINPUT1 REAL 0.0 Service value for measurement on input 1INPUT2 REAL 0.0 Service value for measurement on input 2INPUT3 REAL 0.0 Service value for measurement on input 3INPUT4 REAL 0.0 Service value for measurement on input 4INPUT5 REAL 0.0 Service value for measurement on input 5INPUT6 REAL 0.0 Service value for measurement on input 6INPUT7 REAL 0.0 Service value for measurement on input 7INPUT8 REAL 0.0 Service value for measurement on input 8INPUT9 REAL 0.0 Service value for measurement on input 919.7.3.5 SettingsPID-3791-SETTINGS v5Table 508:I103MEASUSR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 25 Function type (1-255)InfNo 1 - 255 - 1 1 Information number for measurands (1-255)MaxMeasur1 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 1MaxMeasur2 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 2Table continues on next pageSection 19 1MRK 511 408-UUS AStation communication688 Phasor measurement unit RES670 2.2 ANSITechnical manual