19.7.6.4 SignalsPID-6864-INPUTSIGNALS v1Table 513:I103FLTPROT Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting.64_PU_A BOOLEAN 0 Information number 64, pickup phase A65_PU_B BOOLEAN 0 Information number 64, pickup phase B66_PU_C BOOLEAN 0 Information number 64, pickup phase C67_STIN BOOLEAN 0 Information number 67, start residual current IN68_TRGEN BOOLEAN 0 Information number 68, trip general69_TR_A BOOLEAN 0 Information number 69, trip phase A70_TR_B BOOLEAN 0 Information number 70, trip phase B71_TR_C BOOLEAN 0 Information number 71, trip phase C72_TRBKUP BOOLEAN 0 Information number 72, back up trip I>>73_SCL REAL 0 Information number 73, fault location in ohm74_FW BOOLEAN 0 Information number 74, forward/line75_REV BOOLEAN 0 Information number 75, reverse/busbar76_TRANS BOOLEAN 0 Information number 76, signal transmitted77_RECEV BOOLEAN 0 Information number 77, signal received78_ZONE1 BOOLEAN 0 Information number 78, zone 179_ZONE2 BOOLEAN 0 Information number 79, zone 280_ZONE3 BOOLEAN 0 Information number 80, zone 381_ZONE4 BOOLEAN 0 Information number 81, zone 482_ZONE5 BOOLEAN 0 Information number 82, zone 583_ZONE6 BOOLEAN 0 Information number 83, zone 684_STGEN BOOLEAN 0 Information number 84, start general85_BFP BOOLEAN 0 Information number 85, breaker failure86_MTR_A BOOLEAN 0 Information number 86, trip measuring system phaseA87_MTR_B BOOLEAN 0 Information number 87, trip measuring system phaseB88_MTR_C BOOLEAN 0 Information number 88, trip measuring system phaseC89_MTRN BOOLEAN 0 Information number 89, trip measuring system neutralN90_IOC BOOLEAN 0 Information number 90, over current trip, stage low91_IOC BOOLEAN 0 Information number 91, over current trip, stage high92_IEF BOOLEAN 0 Information number 92, ground-fault trip, stage lowTable continues on next page1MRK 511 408-UUS A Section 19Station communicationPhasor measurement unit RES670 2.2 ANSI 693Technical manual