Name Type DescriptionTRST2_A BOOLEAN Trip signal from step2 phase ATRST2_B BOOLEAN Trip signal from step2 phase BTRST2_C BOOLEAN Trip signal from step2 phase CPICKUP BOOLEAN Common pickup signalPU_ST1 BOOLEAN Common pickup signal from step1PU_ST1_A BOOLEAN Pickup signal from step1 phase APU_ST1_B BOOLEAN Pickup signal from step1 phase BPU_ST1_C BOOLEAN Pickup signal from step1 phase CPU_ST2 BOOLEAN Common pickup signal from step2PU_ST2_A BOOLEAN Pickup signal from step2 phase APU_ST2_B BOOLEAN Pickup signal from step2 phase BPU_ST2_C BOOLEAN Pickup signal from step2 phase C9.1.5 SettingsPID-3586-SETTINGS v7Table 150:UV2PTUV (27) Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/EnabledOperationStep1 DisabledEnabled- - Enabled Enable execution of step 1Characterist1 Definite timeInverse curve AInverse curve BProg. inv. curve- - Definite time Selection of time delay curve type for step 1OpMode1 1 out of 32 out of 33 out of 3- - 1 out of 3 Number of phases required for op (1 of 3, 2 of3, 3 of 3) from step 1Pickup1 1.0 - 100.0 %VB 0.1 70.0 Voltage pickup value (Definite-Time &Inverse-Time curve) in % of VBase, step 1t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves forstep 1TD1 0.05 - 1.10 - 0.01 0.05 Time dial multiplier for the inverse time delayfor step 1IntBlkSel1 DisabledBlock of tripBlock all- - Disabled Internal (low level) blocking mode, step 1IntBlkStVal1 1 - 50 %VB 1 20 Voltage setting for internal blocking in % ofVBase, step 1Table continues on next page1MRK 511 408-UUS A Section 9Voltage protectionPhasor measurement unit RES670 2.2 ANSI 273Technical manual