PID-6951-OUTPUTSIGNALS v7Table 405:SSIML Output signalsName Type DescriptionLOCKOUT BOOLEAN Level below lockout level or temperature abovelockout levelLVLLO BOOLEAN Level below lockout levelTEMPLO BOOLEAN Temperature above lockout levelALARM BOOLEAN Level below alarm level or temperature above alarmlevelLVLALM BOOLEAN Level below alarm levelTEMPALM BOOLEAN Temperature above alarm levelLEVEL REAL Level service valueTEMP REAL Temperature of the insulation medium16.3.5 SettingsPID-6951-SETTINGS v7Table 406:SSIML Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnLevelAlmLimit 1.00 - 100.00 - 0.01 5.00 Alarm setting for levelLevelLOLimit 1.00 - 100.00 - 0.01 3.00 Level lockout settingTempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of themediumTempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the mediumtLevelAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for level alarmtLevelLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for level lockout indicationtTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarmtTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockouttResetLevelAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for level alarmtResetLevelLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for level lockouttResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture lockouttResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarmSection 16 1MRK 511 408-UUS AMonitoring530 Phasor measurement unit RES670 2.2 ANSITechnical manual