Name Type DescriptionOUT8 BOOLEAN Output 8OUT9 BOOLEAN Output 9OUT10 BOOLEAN Output 10OUT11 BOOLEAN Output 11OUT12 BOOLEAN Output 12OUT13 BOOLEAN Output 13OUT14 BOOLEAN Output 14OUT15 BOOLEAN Output 15OUT16 BOOLEAN Output 1615.13.5 Setting parameters ABBD8E242451 v3The function does not have any parameters available in local HMI or Protection andControl IED Manager (PCM600)15.13.6 Operation principle SEMOD158385-4 v4With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and theremaining OUTx = 0 for (5≤x≤16).OUTx represents a value when activated. The value of each of the OUTx is inaccordance with the table IB16_1. When not activated the OUTx has the value 0.In the above example when integer 15 is on the input INP the OUT1 has a value =1,OUT2 has a value =2, OUT3 has a value =4 and OUT4 has a value =8. The sum ofthese OUTx is equal to 1 + 2 + 4 + 8 = 15.This follows the general formulae: The sum of the values of all OUTx = 2x-1 where1≤x≤16 will be equal to the integer value on the input INP.The Integer to Boolean 16 conversion function (IB16) will transfer an integer with avalue between 0 to 65535 connected to the input INP to a combination of activatedoutputs OUTx where 1≤x≤16. The sum of the values of all OUTx will then be equal tothe integer on input INP. The values of the different OUTx are according to the tablebelow. When an OUTx is not activated, its value is 0.When all OUTx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to thatinteger 65535 is connected to input INP. The IB16 function is designed for receivingthe integer input locally. If the BLOCK input is activated, it will freeze the logicaloutputs at the last value.Values of each of the different OUTx from function block IB16 for 1≤x≤16.Section 15 1MRK 511 408-UUS ALogic470 Phasor measurement unit RES670 2.2 ANSITechnical manual