15.8.10.1 Function block GUID-13589BAE-38AE-46A1-8E9F-94BCD1CBCBF1 v1TIMERSETQTINPUT ONOFFIEC14000068-1-en.vsdIEC14000068 V1 EN-USFigure 178: TIMERSETQT function15.8.10.2 Signals GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1PID-3816-INPUTSIGNALS v5Table 324:TIMERSETQT Input signalsName Type Default DescriptionINPUT BOOLEAN 0 Input signalPID-3816-OUTPUTSIGNALS v5Table 325:TIMERSETQT Output signalsName Type DescriptionON BOOLEAN Output signal, pick-up delayedOFF BOOLEAN Output signal, drop-out delayed15.8.10.3 SettingsPID-3816-SETTINGS v5Table 326:TIMERSETQT Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/Enabledt 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n15.8.10.4 Technical dataGUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1Table 327:Number of TIMERSETQT instancesLogic block Quantity with cycle time Range or Value Accuracy3 ms 8 ms 100 msTIMERSETQT - 10 30 (0.000–90000.000) s ±0.5% ±10 msSection 15 1MRK 511 408-UUS ALogic458 Phasor measurement unit RES670 2.2 ANSITechnical manual