PID-6950-OUTPUTSIGNALS v6Table 400:SSIMG Output signalsName Type DescriptionLOCKOUT BOOLEAN Pressure below lockout level or temperature abovelockout levelPRESLO BOOLEAN Pressure below lockout levelTEMPLO BOOLEAN Temperature above lockout levelALARM BOOLEAN Pressure below alarm level or temperature abovealarm levelPRESALM BOOLEAN Pressure below alarm levelTEMPALM BOOLEAN Temperature above alarm levelPRESSURE REAL Pressure service valueTEMP REAL Temperature of the insulation medium16.2.5 SettingsPID-6950-SETTINGS v6Table 401:SSIMG Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnPresAlmLimit 1.00 - 100.00 - 0.01 5.00 Alarm setting for pressurePresLOLimit 1.00 - 100.00 - 0.01 3.00 Pressure lockout settingTempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of themediumTempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the mediumtPressureAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for pressure alarmtPressureLO 0.000 - 60.000 s 0.001 0.000 Time delay for pressure lockout indicationtTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarmtTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockouttResetPresAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure alarmtResetPresLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure lockouttResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture lockouttResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarmSection 16 1MRK 511 408-UUS AMonitoring526 Phasor measurement unit RES670 2.2 ANSITechnical manual