PID-6828-OUTPUTSIGNALS v3Table 480:GOOSEDPRCV Output signalsName Type DescriptionDPOUT INTEGER Double point outputDATAVALID BOOLEAN Data valid for double point outputCOMMVALID BOOLEAN Communication valid for double point outputTEST BOOLEAN Test output19.4.7.5 SettingsPID-6828-SETTINGS v3Table 481:GOOSEDPRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/Enabled19.4.7.6 Operation principle GUID-82A1C8A2-827A-40EF-8E58-F573E29E468E v4The DATAVALID output will be HIGH if the incoming message is with valid data.The COMMVALID output will become LOW when the sending IED is under totalfailure condition and the GOOSE transmission from the sending IED does not happen.The TEST output will go HIGH if the sending IED is in test mode.Data Value Data Valid Comm Valid TestIncoming data with q=Normal Updated 1 1 0Incoming data with q=oldData 0 0 1 0Incoming data with q=Invalid 0 0 1 0Incoming data with q=test 0 0 1 1Incoming data with q=test+oldData 0 0 1 1Receiver in block 0 0 1 0Receiver in block and communicationerror0 0 0 0Receiver in test mode and incomingdata with q= NormalUpdated 1 1 0Receiver in test mode and incomingdata with q= TestUpdated 1 1 1Communication Error 0 0 0 01MRK 511 408-UUS A Section 19Station communicationPhasor measurement unit RES670 2.2 ANSI 635Technical manual