The BLOCKED signal is a steady signal and is set when the counter is blocked. Thereare two reasons why the counter is blocked:• The BLOCK input is set, or• The Binary Input Module, where the counter input is situated, is inoperative.The NEW_VAL signal is a pulse signal. The signal is set if the counter value wasupdated since last report.Note, the pulse is short, one cycle.The SCAL_VAL signal consists of scaled value (according to parameter Scale), timeand status information.17.1.8 Technical data IP14092-1 v1M13404-2 v5Table 447:PCFCNT technical dataFunction Setting range AccuracyInput frequency See Binary Input Module (BIM) -Cycle time for report ofcounter value(1–3600) s -17.2 Function for energy calculation and demand handlingETPMMTR SEMOD153638-1 v217.2.1 IdentificationSEMOD175537-2 v4Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberFunction for energy calculation anddemand handlingETPMMTR W_Varh -1MRK 511 408-UUS A Section 17MeteringPhasor measurement unit RES670 2.2 ANSI 599Technical manual