Name Values (Range) Unit Step Default DescriptionGiNo1 ExcludedIncluded- - Included Response and status change (GI)GiNo2 ExcludedIncluded- - Included Response and status change (GI)GiNo3 ExcludedIncluded- - Included Response and status change (GI)GiNo4 ExcludedIncluded- - Included Response and status change (GI)GiNo5 ExcludedIncluded- - Included Response and status change (GI)GiNo6 ExcludedIncluded- - Included Response and status change (GI)GiNo7 ExcludedIncluded- - Included Response and status change (GI)GiNo8 ExcludedIncluded- - Included Response and status change (GI)GUID-86DE9DBA-BE2F-4CC9-B447-1D2D86849EFF v2The FunctionType parameter associates a particular instance of the function blockwith a FUN. Refer to the IEC 60870-5-103 standard for details.The InfNon parameters are used to associate each individual input signal with auserdefined INF. Refer to the IEC 60870-5-103 standard for details.The TypNon parameters determine if messages use absolute or relative time. Thisadheres to the TYPE IDENTIFICATION (TYP) message types 1 (time-taggedmessage) and 2 (time-tagged message with relative time) of the IEC 60870-5-103standard.The GiNon parameters determine whether a message is sent as a part of a GI reply ornot. Refer to the IEC 60870-5-103 standard for details.19.7.10 Function commands for IEC 60870-5-103 I103CMD19.7.10.1 Functionality GUID-973929FE-292B-42A5-ACF9-BC95E2B16AE1 v2I103CMD is a command function block in control direction with pre-defined outputsignals. The signals are in steady state, not pulsed, and stored in the IED in case ofrestart.1MRK 511 408-UUS A Section 19Station communicationPhasor measurement unit RES670 2.2 ANSI 699Technical manual