23.4.1.2 Mounting procedure for flush mounting M11942-2 v51563IEC16000080=1=en.vsd24IEC16000080 V1 EN-USFigure 334: Flush mounting details.PosNo Description Quantity Type1 Sealing strip, used to obtain IP54class. The sealing strip is factorymounted between the case andfront plate.- -2 Fastener 2 -3 Groove - -4 Screw 4 M3x8 mm5 Joining point of sealing strip - -6 Panel - -23.4.2 19” panel rack mounting IP10313-1 v123.4.2.1 Overview SEMOD127656-5 v4All IED sizes can be mounted in a standard 19” cubicle rack by using a suitably sizedmounting kit consisting of two mounting angles, their fastening screws and washers.The mounting angles are reversible which enables mounting of IED size 1/2 x 19” or3/4 x 19” either to the left or the right side of the cubicle.1MRK 511 408-UUS A Section 23IED hardwarePhasor measurement unit RES670 2.2 ANSI 861Technical manual