17.2.5 SettingsPID-6872-SETTINGS v3Table 450:ETPMMTR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/EnabledEnaAcc DisabledEnabled- - Disabled Activate the accumulation of energy valuestEnergy 1 Minute5 Minutes10 Minutes15 Minutes30 Minutes60 Minutes180 Minutes- - 1 Minute Time interval for energy calculationtEnergyOnPls 0.100 - 60.000 s 0.001 1.000 Energy accumulated pulse ON time in secstEnergyOffPls 0.100 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time in secsEAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward accumulatedenergy valueEARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse accumulatedenergy valueERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forwardaccumulated energy valueERRAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverseaccumulated energy valueTable 451:ETPMMTR Non group settings (advanced)Name Values (Range) Unit Step Default DescriptionEALim 0.001 -10000000000.000MWh 0.001 1000000.000 Active energy limitERLim 0.001 -10000000000.000MVArh 0.001 1000.000 Reactive energy limitEnZeroClamp DisabledEnabled- - Enabled Enable of zero point clamping detectionfunctionLevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active PowerLevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive PowerDirEnergyAct ForwardReverse- - Forward Direction of active energy flow Forward/ReverseDirEnergyReac ForwardReverse- - Forward Direction of reactive energy flow Forward/ReverseEAFPrestVal 0.000 -100000000.000MWh 0.001 0.000 Preset Initial value for forward active energyTable continues on next pageSection 17 1MRK 511 408-UUS AMetering602 Phasor measurement unit RES670 2.2 ANSITechnical manual