8.6.5 SettingsPID-3709-SETTINGS v6Table 134:GUPPDUP (37) Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/EnabledOpMode1 DisabledUnderPower- - UnderPower Operation mode for stage 1 Off / OnPower1 0.0 - 500.0 %SB 0.1 1.0 Stage 1 underpower setting in Angle1direction in % of SBaseAngle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power senistivitystage 1TripDelay1 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 1DropDelay1 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 1OpMode2 DisabledUnderPower- - UnderPower Operation mode for stage 2 Off / OnPower2 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 2 in % of SBaseAngle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power senistivitystage 2TripDelay2 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 2DropDelay2 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 2Table 135:GUPPDUP (37) Group settings (advanced)Name Values (Range) Unit Step Default DescriptionTD 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for powermeasurement, P and QHysteresis1 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in % SBaseHysteresis2 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in % SBaseIMagComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates currenterror at 5% of IrIMagComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates currenterror at 30% of IrIMagComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates currenterror at 100% of IrVMagComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates voltageerror at 5% of UrVMagComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates voltageerror at 30% of UrVMagComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates voltageerror at 100% of UrTable continues on next pageSection 8 1MRK 511 408-UUS ACurrent protection254 Phasor measurement unit RES670 2.2 ANSITechnical manual