When EnaAbs is set as absolute comparison and SetValue is set lessthan 0.2% of the set unit then INLOW output will never pickups.During the above mentioned condition, due to marginal value foravoiding oscillations of function outputs, the INLOW output will neverset.15.17.7 Technical dataGUID-62792FCB-B436-4034-9A08-C9FF918FF547 v1REALCOMP function can compare the values from milli value level to giga valuelevel and the maximum expectable accuracy level from the function is 10 μ.GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v3Table 362:Number of REALCOMP instancesFunction Quantity with cycle time3 ms 8 ms 100 msREALCOMP 10 10 10Section 15 1MRK 511 408-UUS ALogic486 Phasor measurement unit RES670 2.2 ANSITechnical manual