PID-6737-OUTPUTSIGNALS v2Table 374:VNMMXU Output signalsName Type DescriptionVA REAL VA Amplitude, magnitude of reported valueVA_RANGE INTEGER VAAmplitude rangeVA_ANGL REAL VA Angle, magnitude of reported valueVB REAL VB Amplitude, magnitude of reported valueVB_RANGE INTEGER VB Amplitude rangeVB_ANGL REAL VB Angle, magnitude of reported valueVC REAL VC Amplitude, magnitude of reported valueVC_RANGE INTEGER VC Amplitude rangeVC_ANGL REAL V_C Angle, magnitude of reported value16.1.5 Settings SEMOD130322-4 v7The available setting parameters of the measurement function (MMXU, MSQI) aredepending on the actual hardware (TRM) and the logic configuration made inPCM600.These six functions are not handled as a group, so parameter settings are only availablein the first setting group.The following terms are used in the Unit and Description columns:• VBase (VB): Base voltage in primary kV. This voltage is used as reference forvoltage setting. It can be suitable to set this parameter to the rated primary voltagesupervised object.• IBase (IB): Base current in primary A. This current is used as reference for currentsetting. It can be suitable to set this parameter to the rated primary current of thesupervised object.• SBase (SB): Base setting for power values in MVA.PID-6713-SETTINGS v3Table 375:CVMMXN Non group settings (basic)Name Values (Range) Unit Step Default DescriptionSLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBaseSLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBaseSMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBaseSMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBaseTable continues on next page1MRK 511 408-UUS A Section 16MonitoringPhasor measurement unit RES670 2.2 ANSI 495Technical manual