Table 208:FUFSPVC Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Valuegroups13.2.6 Monitored dataPID-3492-MONITOREDDATA v8Table 209:FUFSPVC Monitored dataName Type Values (Range) Unit Description3I0 REAL - A Magnitude of zero sequencecurrent3I2 REAL - A Magnitude of negativesequence current3V0 REAL - kV Magnitude of zero sequencevoltage3V2 REAL - kV Magnitude of negativesequence voltage13.2.7 Operation principle13.2.7.1 Zero and negative sequence detection M13677-3 v5The zero and negative sequence function continuously measures the currents andvoltages in all three phases and calculates, see figure 130:• the zero-sequence voltage 3V0• the zero-sequence current 3I0• the negative sequence current 3I2• the negative sequence voltage 3V2The measured signals are compared with their respective set values 3V0PU and 3I0PU,3V2PU and 3I2PU.The function enable the internal signal FuseFailDetZeroSeq if the measured zero-sequence voltage is higher than the set value 3V0PU and the measured zero-sequencecurrent is below the set value 3I0PU.The function enable the internal signal FuseFailDetNegSeq if the measured negativesequence voltage is higher than the set value 3V2PU and the measured negativesequence current is below the set value 3I2PU.Section 13 1MRK 511 408-UUS ASecondary system supervision370 Phasor measurement unit RES670 2.2 ANSITechnical manual