Name Type DescriptionBI4 BOOLEAN Binary input 4 valueBI5 BOOLEAN Binary input 5 valueBI6 BOOLEAN Binary input 6 valueBI7 BOOLEAN Binary input 7 valueBI8 BOOLEAN Binary input 8 valueBI9 BOOLEAN Binary input 9 valueBI10 BOOLEAN Binary input 10 valueBI11 BOOLEAN Binary input 11 valueBI12 BOOLEAN Binary input 12 valueBI13 BOOLEAN Binary input 13 valueBI14 BOOLEAN Binary input 14 valueBI15 BOOLEAN Binary input 15 valueBI16 BOOLEAN Binary input 16 valueOSCWRN BOOLEAN Oscillation warning23.2.7.4 SettingsPID-3473-SETTINGS v2Table 638:BIM Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Enabled Operation Disabled/EnabledDebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputsOscBlock 1 - 40 Hz 1 40 Oscillation block limitOscRelease 1 - 30 Hz 1 30 Oscillation release limit23.2.7.5 Monitored dataPID-3473-MONITOREDDATA v2Table 639:BIM Monitored dataName Type Values (Range) Unit DescriptionSTATUS BOOLEAN 0=Ok1=Error- Binary input module status1MRK 511 408-UUS A Section 23IED hardwarePhasor measurement unit RES670 2.2 ANSI 817Technical manual