Name Type DescriptionSMPLLOST BOOLEAN Fatal error or recovery state after fatal error. High ifany subscribed channel has bad quality or TEST whileIED not in test mode.MUSYNCH BOOLEAN MU not synced or MU clock not synced to same clockas IEDTESTMODE BOOLEAN Quality of one or more subscribed analogue channelsis TESTSIMMODE BOOLEAN MU delivers simulated data accepted by IEDI1QUALITY INTEGER Binary coded quality information for I1I2QUALITY INTEGER Binary coded quality information for I2I3QUALITY INTEGER Binary coded quality information for I3I4QUALITY INTEGER Binary coded quality information for I0U1QUALITY INTEGER Binary coded quality information for VAU2QUALITY INTEGER Binary coded quality information for VBU3QUALITY INTEGER Binary coded quality information for VCU4QUALITY INTEGER Binary coded quality information for 3V019.5.4 Settings SEMOD166625-1 v2PID-6850-SETTINGS v3Table 498:MU1_HW Non group settings (basic)Name Values (Range) Unit Step Default DescriptionCTStarPoint1 FromObjectToObject- - ToObject ToObject= towards protected object,FromObject= the oppositeCTStarPoint2 FromObjectToObject- - ToObject ToObject= towards protected object,FromObject= the oppositeCTStarPoint3 FromObjectToObject- - ToObject ToObject= towards protected object,FromObject= the oppositeCTStarPoint4 FromObjectToObject- - ToObject ToObject= towards protected object,FromObject= the opposite1MRK 511 408-UUS A Section 19Station communicationPhasor measurement unit RES670 2.2 ANSI 653Technical manual