8.3.5 SettingsPID-4151-SETTINGS v4Table 108:NS4PTOC (46I2) Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/EnabledEnDir DisableEnable- - Enable Enabling the Directional calculationAngleRCA -180 - 180 Deg 1 65 Relay characteristic angle (RCA)VPolMin 1 - 100 %VB 1 5 Minimum voltage level for polarization in % ofVBaseI2>Dir 1 - 100 %IB 1 10 Residual current level in % of IBase forDirection releaseDirModeSel1 DisabledNon-directionalForwardReverse- - Non-directional Directional mode of step 1 (Disabled, Nondir,Forward, Reverse)Characterist1 ANSI Ext. inv.ANSI Very inv.ANSI Norm. inv.ANSI Mod. inv.ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.IEC Def. TimeReservedProgrammableRI typeRD type- - ANSI Def. Time Time delay characteristic for step 1I2-1> 1 - 2500 %IB 1 100 Negative sequence current op level for step 1in % of IBaset1 0.000 - 60.000 s 0.001 0.000 Time delay of step 1 when definite time char.is selectedTD1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 1 selected timecharacteristicIMin1 1.00 - 10000.00 %IB 1.00 100.00 Minimum current for step 1t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse timecharacteristic step 1MultPU1 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting valuefor step 1Table continues on next pageSection 8 1MRK 511 408-UUS ACurrent protection216 Phasor measurement unit RES670 2.2 ANSITechnical manual