PID-4114-OUTPUTSIGNALS v5Table 36:LEDGEN Output signalsName Type DescriptionNEWIND BOOLEAN New indication signal if any LED indication input is setACK BOOLEAN A pulse is provided when the LEDs are acknowledgedPID-1697-INPUTSIGNALS v18Table 37:GRP1_LED1 Input signalsName Type Default DescriptionHM1L01R BOOLEAN 0 Red indication of LED1, local HMI alarm group 1HM1L01Y BOOLEAN 0 Yellow indication of LED1, local HMI alarm group 1HM1L01G BOOLEAN 0 Green indication of LED1, local HMI alarm group 15.3.4 SettingsPID-4114-SETTINGS v6Table 38:LEDGEN Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Enabled Operation Disabled/EnabledtRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance lengtht_MaxTripDelay 0.1 - 100.0 s 0.1 1.0 Maximum time for the definition of adisturbancePID-1697-SETTINGS v18Table 39:GRP1_LED1 Non group settings (basic)Name Values (Range) Unit Step Default DescriptionSequenceType Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S- - Follow-S Sequence type for LED 1, local HMI alarmgroup 1LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarm group1 is offLabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarm group1 is redLabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarm group1 is yellowLabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarm group1 is greenSection 5 1MRK 511 408-UUS ALocal Human-Machine-Interface LHMI78 Phasor measurement unit RES670 2.2 ANSITechnical manual