3.9 Parameters 8-** Communications andOptions3.9.1 8-0* General Settings8-01 Control SiteThe setting in this parameter overrides the settings inparameter 8-50 Coasting Select to parameter 8-56 Preset ReferenceSelect.Option: Function:[0] * Digital and ctrl.word Use both digital input andcontrol word.[1] Digital only Use digital inputs only.[2] Controlword only Use control word only.8-02 Control Word SourceOption: Function:NOTICEThis parameter cannot be adjustedwhile the motor is running.Select the source of the control word: 1 of 2serial interfaces or 4 installed options. Duringinitial power-up, the frequency converterautomatically sets this parameter to [3] OptionA if it detects a valid fieldbus option installedin slot A. If the option is removed, thefrequency converter detects a change in theconfiguration, sets parameter 8-02 ControlSource to default setting [1] FC Port, and thefrequency converter then trips. If an option isinstalled after initial power-up, the setting ofparameter 8-02 Control Source does notchange, but the frequency converter trips andshows alarm 67, Option Changed.[0] None[1] FC RS485[2] FC USB[3] * Option A[4] Option B[5] Option C0[6] Option C1[30] External Can8-03 Control Timeout TimeRange: Function:Sizerelated*[1 -18000 s]Enter the maximum time expected to passbetween the reception of 2 consecutivetelegrams. If this time is exceeded, itindicates that the serial communication hasstopped. The function selected inparameter 8-04 Control Timeout Function isthen carried out. A valid control wordtriggers the timeout counter. The minimum8-03 Control Timeout TimeRange: Function:value that can be set depends on the actualfrequency converter used.The object list holds information on theobjects that triggers the control timeout:• Analog outputs• Binary outputs• AV0• AV1• AV2• AV4• BV1• BV2• BV3• BV4• BV5• Multistate outputs8-04 Control Timeout FunctionSelect the timeout function. The timeout function is activatedwhen the control word fails to be updated within the timeperiod specified in parameter 8-03 Control Timeout Time. [20] N2Override Release only appears after setting the Metasys N2protocol.To change the set-up after a timeout, configure as follows:1. Set parameter 0-10 Active Set-up to [9] Multi set-up.2. Select the relevant link in parameter 0-12 This Set-upLinked to.Option: Function:[0] * Off Resumes control via fieldbus(fieldbus or standard), using themost recent control word.[1] Freeze output Freezes output frequency untilcommunication resumes.[2] Stop Stops with auto restart whencommunication resumes.[3] Jogging Runs the motor at jog frequencyuntil communication resumes.[4] Max. speed Runs the motor at maximumfrequency until communicationresumes.[5] Stop and trip Stops the motor, then resets thefrequency converter to restart via:• Fieldbus.• [Reset].• Digital input.Parameter Description VLT® AQUA Drive FC 202100 Danfoss A/S © 05/2018 All rights reserved. MG20OB0233