4.1.8 6-** Analog In/OutParam-eter #Parameter description Default value 4 set-up Change duringoperationConversionindexType6-0* Analog I/O Mode6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint86-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint86-1* Analog Input 536-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 Int166-11 Terminal 53 High Voltage 10 V All set-ups TRUE -2 Int166-12 Terminal 53 Low Current 4 mA All set-ups TRUE -5 Int166-13 Terminal 53 High Current 20 mA All set-ups TRUE -5 Int166-14 Terminal 53 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int326-15 Terminal 53 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int326-16 Terminal 53 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint166-17 Terminal 53 Live Zero [1] Enabled All set-ups TRUE - Uint86-2* Analog Input 546-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 Int166-21 Terminal 54 High Voltage 10 V All set-ups TRUE -2 Int166-22 Terminal 54 Low Current 4 mA All set-ups TRUE -5 Int166-23 Terminal 54 High Current 20 mA All set-ups TRUE -5 Int166-24 Terminal 54 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int326-25 Terminal 54 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int326-26 Terminal 54 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint166-27 Terminal 54 Live Zero [1] Enabled All set-ups TRUE - Uint86-3* Analog Input X30/116-30 Terminal X30/11 Low Voltage 0.07 V All set-ups TRUE -2 Int166-31 Terminal X30/11 High Voltage 10 V All set-ups TRUE -2 Int166-34 Term. X30/11 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int326-35 Term. X30/11 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int326-36 Term. X30/11 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint166-37 Term. X30/11 Live Zero [1] Enabled All set-ups TRUE - Uint86-4* Analog Input X30/126-40 Terminal X30/12 Low Voltage 0.07 V All set-ups TRUE -2 Int166-41 Terminal X30/12 High Voltage 10 V All set-ups TRUE -2 Int166-44 Term. X30/12 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int326-45 Term. X30/12 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int326-46 Term. X30/12 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint166-47 Term. X30/12 Live Zero [1] Enabled All set-ups TRUE - Uint86-5* Analog Output 426-50 Terminal 42 Output[100] Output freq.0-100 All set-ups TRUE - Uint86-51 Terminal 42 Output Min Scale 0% All set-ups TRUE -2 Int166-52 Terminal 42 Output Max Scale 100% All set-ups TRUE -2 Int166-53 Terminal 42 Output Bus Control 0% All set-ups TRUE -2 N26-54 Terminal 42 Output Timeout Preset 0% 1 set-up TRUE -2 Uint166-55 Terminal 42 Output Filter [0] Off 1 set-up TRUE - Uint86-6* Analog Output X30/86-60 Terminal X30/8 Output [0] No operation All set-ups TRUE - Uint86-61 Terminal X30/8 Min. Scale 0% All set-ups TRUE -2 Int166-62 Terminal X30/8 Max. Scale 100% All set-ups TRUE -2 Int166-63 Terminal X30/8 Output Bus Control 0% All set-ups TRUE -2 N26-64Terminal X30/8 Output TimeoutPreset 0% 1 set-up TRUE -2 Uint16Parameter Lists VLT® AQUA Drive FC 202258 Danfoss A/S © 05/2018 All rights reserved. MG20OB0244