4.1.9 8-** Comm. and OptionsParam-eter #Parameter description Default value 4 set-up Change duringoperationConversionindexType8-0* General Settings8-01 Control Site[0] Digital andctrl.word All set-ups TRUE - Uint88-02 Control Source ExpressionLimit All set-ups TRUE - Uint88-03 Control Timeout Time ExpressionLimit 1 set-up TRUE -1 Uint328-04 Control Timeout Function [0] Off 1 set-up TRUE - Uint88-05 End-of-Timeout Function [1] Resume set-up 1 set-up TRUE - Uint88-06 Reset Control Timeout [0] Do not reset All set-ups TRUE - Uint88-07 Diagnosis Trigger [0] Disable 2 set-ups TRUE - Uint88-08 Readout Filtering ExpressionLimit All set-ups TRUE - Uint88-1* Control Settings8-10 Control Profile [0] FC profile All set-ups TRUE - Uint88-13 Configurable Status Word STW [1] Profile Default All set-ups TRUE - Uint88-14 Configurable Control Word CTW [1] Profile default 2 set-ups TRUE - Uint88-17Configurable Alarm andWarningword [0] Off All set-ups TRUE - Uint168-3* FC Port Settings8-30 Protocol [0] FC 1 set-up TRUE - Uint88-31 Address ExpressionLimit 1 set-up TRUE 0 Uint88-32 Baud Rate ExpressionLimit 1 set-up TRUE - Uint88-33 Parity/Stop Bits ExpressionLimit 1 set-up TRUE - Uint88-35 Minimum Response Delay 10 ms 1 set-up TRUE -3 Uint168-36 Max Response Delay ExpressionLimit 1 set-up TRUE -3 Uint168-37 Maximum Inter-Char Delay ExpressionLimit 1 set-up TRUE -5 Uint168-4* FC MC protocol set8-40 Telegram Selection[1] Standardtelegram 1 2 set-ups TRUE - Uint88-42 PCD Write Configuration ExpressionLimit 2 set-ups TRUE - Uint168-43 PCD Read Configuration ExpressionLimit 2 set-ups TRUE - Uint168-5* Digital/Bus8-50 Coasting Select [3] Logic OR All set-ups TRUE - Uint88-51 Quick Stop Select [4] Disabled All set-ups TRUE - Uint88-52 DC Brake Select ExpressionLimit All set-ups TRUE - Uint88-53 Start Select [3] Logic OR All set-ups TRUE - Uint88-54 Reversing Select [0] Digital input All set-ups TRUE - Uint88-55 Set-up Select [3] Logic OR All set-ups TRUE - Uint88-56 Preset Reference Select [3] Logic OR All set-ups TRUE - Uint88-7* BACnet8-70 BACnet Device Instance 1 N/A 1 set-up TRUE 0 Uint328-72 MS/TP Max Masters 127 N/A 1 set-up TRUE 0 Uint88-73 MS/TP Max Info Frames 1 N/A 1 set-up TRUE 0 Uint168-74 "I-Am" Service[0] Send at power-up 1 set-up TRUE - Uint88-75 Initialisation Password ExpressionLimit 1 set-up TRUE 0 VisStr[20]8-8* FC Port Diagnostics8-80 Bus Message Count 0 N/A All set-ups TRUE 0 Uint328-81 Bus Error Count 0 N/A All set-ups TRUE 0 Uint328-82 Slave Message Rcvd 0 N/A All set-ups TRUE 0 Uint328-83 Slave Error Count 0 N/A All set-ups TRUE 0 Uint328-9* Bus Jog/FeedbackParameter Lists VLT® AQUA Drive FC 202260 Danfoss A/S © 05/2018 All rights reserved. MG20OB0244