0-20 Display Line 1.1 SmallOption: Function:[1613] Frequency Motor frequency, that is the outputfrequency from the frequency converterin Hz.[1614] Motor Current Phase current of the motor measured aseffective value.[1615] Frequency [%] Motor frequency, that is the outputfrequency from the frequency converterin percent.[1616] Torque [Nm] Present motor load as a percentage ofthe rated motor torque.[1617]*Speed [RPM] Speed in RPM (revolutions per minute),that is the motor shaft speed in closedloop based on the entered motornameplate data, the output frequency,and the load on the frequencyconverter.[1618] Motor Thermal Thermal load on the motor calculatedby the ETR function. See also parametergroup 1-9* Motor Temperature.[1619] KTY sensortemperature[1620] Motor Angle[1622] Torque [%] Shows the actual torque produced inpercentage.[1625] Torque [Nm]High[1630] DC LinkVoltageDC-link voltage in the frequencyconverter.[1632] Brake Energy /s Present brake power transferred to anexternal brake resistor.Shows an instant value.[1633] BrakeEnergy /2 minBrake power transferred to an externalbrake resistor. The average power iscalculated continuously for the mostrecent 120 s.[1634] Heatsink Temp. Present heat sink temperature of thefrequency converter. The cutout limit is95 ±5 °C. Cutting back in occurs at 70±5 °C.[1635] InverterThermalPercentage load of the inverters.[1636] Inv. Nom.CurrentNominal current of the frequencyconverter.[1637] Inv. Max.CurrentMaximum current of the frequencyconverter.[1638] SL ControllerStateState of the event executed by thecontrol.[1639] Control CardTemp.Temperature of the control card.0-20 Display Line 1.1 SmallOption: Function:[1650] ExternalReferenceSum of the external reference as apercentage, that is the sum of analog,pulse, and bus.[1651] PulseReference[1652] Feedback [Unit] Signal value in units from theprogrammed digital inputs.[1653] Digi PotReferenceView the contribution of the digitalpotentiometer to the actual referencefeedback.[1660] Digital Input Shows the status of the digital inputs.Signal low=0, signal high=1.Regarding order, seeparameter 16-60 Digital Input. Bit 0 is atthe extreme right.[1661] Terminal 53Switch SettingSetting of input terminal 53. Current=0,voltage=1.[1662] Analog Input53Actual value at input 53 either as areference or protection value.[1663] Terminal 54Switch SettingSetting of input terminal 54. Current=0,voltage=1.[1664] Analog Input54Actual value at input 54 either asreference or protection value.[1665] Analog Output42 [mA]Actual value at output 42 in mA. Useparameter 6-50 Terminal 42 Output toselect the variable to be show in output42.[1666] Digital Output[bin]Binary value of all digital outputs.[1667] Freq. Input #29[Hz]Actual value of the frequency applied atterminal 29 as a pulse input.[1668] Freq. Input #33[Hz]Actual value of the frequency applied atterminal 33 as a pulse input.[1669] Pulse Output#27 [Hz]Actual value of pulses applied toterminal 27 in digital output mode.[1670] Pulse Output#29 [Hz]Actual value of pulses applied toterminal 29 in digital output mode.[1671] Relay Output[bin]View the setting of all relays.[1672] Counter A View the present value of counter A.[1673] Counter B View the present value of counter B.[1674] Prec. StopCounter[1675] Analog InX30/11Actual value of the signal on inputX30/11 (VLT® General Purpose I/O MCB101, optional).Parameter Description Programming GuideMG20OB02 Danfoss A/S © 05/2018 All rights reserved. 313 3