Illustration 2.25 Main Menu/Quick Set-up2.2.18 LCP KeysKeys for local control are at the bottom of the LCP.e30bp046.12HandOn Off AutoOn ResetIllustration 2.26 LCP Keys[Hand On]Enables control of the frequency converter via the LCP.[Hand On] also starts the motor and it is now possible toenter the motor speed data with the navigation keys. Thekey can be selected as [1] Enable or [0] Disable viaparameter 0-40 [Hand on] Key on LCP.External stop signals activated with control signals, or afieldbus, override a start command via the LCP.The following control signals are still active when [HandOn] is activated:• [Hand On] - [Off] - [Auto On].• Reset.• Coast stop inverse.• Reversing.• Set-up select lsb - Set-up select msb.• Stop command from serial communication.• Quick stop.• DC brake.[Off]Stops the connected motor. The key can be selected as [1]Enable or [0] Disable via parameter 0-41 [Off] Key on LCP.If no external stop function is selected and the [Off] key isinactive, stop the motor by disconnecting the voltage.[Auto On]Enables control of the frequency converter via the controlterminals and/or serial communication. When a start signalis applied on the control terminals and/or the bus, thefrequency converter starts. The key can be selected as [1]Enable or [0] Disable via parameter 0-42 [Auto on] Key onLCP.NOTICEAn active HAND-OFF-AUTO signal via the digital inputshas higher priority than the control keys [Hand On] and[Auto On].[Reset]Used for resetting the frequency converter after an alarm(trip). It can be selected as [1] Enable or [0] Disable viaparameter 0-43 [Reset] Key on LCP.2.3.1 Initialization to Default SettingsInitialize the frequency converter to default settings in 2ways.Recommended initialization (viaparameter 14-22 Operation Mode)1. Select parameter 14-22 Operation Mode.2. Press [OK].3. Select [2] initialization.4. Press [OK].5. Disconnect the mains supply and wait until thedisplay turns off.6. Reconnect the mains supply. The frequencyconverter is now reset.Parameter 14-22 Operation Mode initializes all except:• Parameter 14-50 RFI Filter.• Parameter 8-30 Protocol.• Parameter 8-31 Address.• Parameter 8-32 FC Port Baud Rate.• Parameter 8-35 Minimum Response Delay.• Parameter 8-36 Max Response Delay.• Parameter 8-37 Max Inter-Char Delay.• Parameter 15-00 Operating hours toparameter 15-05 Over Volt's.• Parameter 15-20 Historic Log: Event toparameter 15-22 Historic Log: Time.• Parameter 15-30 Fault Log: Error Code toparameter 15-32 Alarm Log: Time.How to Program VLT® AQUA Drive FC 20224 Danfoss A/S © 05/2018 All rights reserved. MG20OB0222