3.14 Parameters 15-** Drive InformationParameter group containing frequency converterinformation such as operating data, hardware configu-ration, and software versions.3.14.1 15-0* Operating Data15-00 Operating hoursRange: Function:0 h* [0 - 2147483647 h] View how many hours the frequencyconverter has run. The value is savedwhen the frequency converter isturned off.15-01 Running HoursRange: Function:0 h* [0 -2147483647 h]View how many hours the motor has run.Reset the counter inparameter 15-07 Reset Running HoursCounter. The value is saved when thefrequency converter is turned off.15-02 kWh CounterRange: Function:0 kWh* [0 -2147483647kWh]Register the power consumption ofthe motor as an average value over 1hour. Reset the counter inparameter 15-06 Reset kWh Counter.15-03 Power Up'sRange: Function:0* [0 - 2147483647 ] View the number of times the frequencyconverter has been powered up.15-04 Over Temp'sRange: Function:0* [0 - 65535 ] View the number of frequency convertertemperature faults.15-05 Over Volt'sRange: Function:0* [0 - 65535 ] View the number of frequency converterovervoltages.15-06 Reset kWh CounterOption: Function:[0] * Do not reset No reset of the kWh counter is required.[1] Reset counter Press [OK] to reset the kWh counter to 0(see parameter 15-02 kWh Counter).15-07 Reset Running Hours CounterOption: Function:[0] * Do notresetNo reset of the running hours counter isrequired.[1] ResetcounterSelect [1] Reset counter and press [OK] to resetthe running hours counter(parameter 15-01 Running Hours) andparameter 15-08 Number of Starts to 0 (seealso parameter 15-01 Running Hours).15-08 Number of StartsRange: Function:0* [0 -2147483647 ]NOTICEThis parameter is reset when resettingparameter 15-07 Reset Running HoursCounter.This is a readout parameter only. Thecounter shows the number of starts andstops caused by a normal start/stopcommand and/or when entering/leavingsleep mode.3.14.2 15-1* Data Log SettingsThe data log enables continuous logging of up to 4 datasources (parameter 15-10 Logging Source) at individual rates(parameter 15-11 Logging Interval). A trigger event(parameter 15-12 Trigger Event) and window(parameter 15-14 Samples Before Trigger) are used to startand stop the logging conditionally.15-10 Logging SourceArray [4]Option: Function:[0] * None[1472] VLT Alarm Word[1473] VLT Warning Word[1474] VLT Ext. Status Word[1600] Control Word[1601] Reference [Unit][1602] Reference %[1603] Status Word[1610] Power [kW][1611] Power [hp][1612] Motor Voltage[1613] Frequency[1614] Motor Current[1616] Torque [Nm][1617] Speed [RPM][1618] Motor Thermal[1622] Torque [%][1625] Torque [Nm] High[1630] DC Link VoltageParameter Description Programming GuideMG20OB02 Danfoss A/S © 05/2018 All rights reserved. 1413 3