8-55 Set-up SelectSelect the trigger for the set-up selection.Option: Function:[0] Digital input A digital input triggers the set-up selection.[1] Bus A serial communication port or the fieldbustriggers the set-up selection.[2] Logic AND The fieldbus/serial communication port and adigital input trigger the set-up selection.[3] * Logic OR The fieldbus/serial communication port or adigital input triggers the set-up selection.8-56 Preset Reference SelectOption: Function:Select the trigger for the preset referenceselection.[0] DigitalinputA digital input triggers the preset referenceselection.[1] Bus A serial communication port or the fieldbustriggers the preset reference selection.[2] Logic AND The fieldbus/serial communication port and adigital input trigger the preset referenceselection.[3] * Logic OR The fieldbus/serial communication port or adigital input triggers the preset referenceselection.3.9.6 8-8* FC Port DiagnosticsThese parameters are used for monitoring the buscommunication via the frequency converter port.8-80 Bus Message CountRange: Function:0* [0 - 4294967295 ] This parameter shows the number ofvalid telegrams detected on the bus.8-81 Bus Error CountArray [6]Range: Function:0* [0 - 4294967295 ] This parameter shows the number oftelegrams with faults (for example CRCfault) detected on the bus.8-82 Slave Message RcvdRange: Function:0* [0 - 4294967295 ] This parameter shows the number ofvalid telegrams addressed to the slavesent by the frequency converter.8-83 Slave Error CountRange: Function:0* [0 - 4294967295 ] This parameter shows the number oferror telegrams, which are not executedby the frequency converter.3.9.7 8-9* Bus Jog8-94 Bus Feedback 1Range: Function:0* [-200 -200 ]Write feedback to this parameter via the serialcommunication port or fieldbus option. Selectthis parameter as a feedback source inparameter 20-00 Feedback 1 Source,parameter 20-03 Feedback 2 Source, orparameter 20-06 Feedback 3 Source.8-95 Bus Feedback 2Range: Function:0* [-200 - 200 ] See parameter 8-94 Bus Feedback 1 for furtherdetails.8-96 Bus Feedback 3Range: Function:0* [-200 - 200 ] See parameter 8-94 Bus Feedback 1 for furtherdetails.8-97 Response Error CodesRange: Function:0* [0 - 0 ]3.10 Parameters 9-** PROFIBUSFor PROFIBUS parameter descriptions, see the VLT®PROFIBUS DP MCA 101 Programming Guide.Parameter Description Programming GuideMG20OB02 Danfoss A/S © 05/2018 All rights reserved. 1093 3