5-54 Pulse Filter Time Constant #29Range: Function:100ms*[5 -1000 ms]NOTICEThis parameter cannot be adjustedwhile the motor is running.Enter the pulse filter time constant. Thepulse filter dampens oscillations of thefeedback signal, which is an advantage ifthere is a lot of noise in the system. A hightime constant value results in betterdampening, but also increases the timedelay through the filter.5-55 Term. 33 Low FrequencyRange: Function:100 Hz* [0 - 110000Hz]Enter the low frequency correspondingto the low motor shaft speed (that islow reference value) inparameter 5-57 Term. 33 Low Ref./Feedb.Value.5-56 Term. 33 High FrequencyRange: Function:100 Hz* [0 - 110000Hz]Enter the high frequency correspondingto the high motor shaft speed (that ishigh reference value) inparameter 5-58 Term. 33 High Ref./Feedb.Value.5-57 Term. 33 Low Ref./Feedb. ValueRange: Function:0 ReferenceFeed-backUnit*[-999999.999 -999999.999ReferenceFeed-backUnit]Enter the low referencevalue [RPM] for the motorshaft speed. This is alsothe low feedback value,see alsoparameter 5-52 Term. 29Low Ref./Feedb. Value.5-58 Term. 33 High Ref./Feedb. ValueRange: Function:100 Reference-FeedbackUnit*[-999999.999 -999999.999ReferenceFeed-backUnit]Enter the high referencevalue [RPM] for the motorshaft speed. See alsoparameter 5-53 Term. 29High Ref./Feedb. Value.5-59 Pulse Filter Time Constant #33Range: Function:100ms*[5 - 1000ms]NOTICEThis parameter cannot be adjustedwhile the motor is running.5-59 Pulse Filter Time Constant #33Range: Function:Enter the pulse filter time constant. Thelow-pass filter reduces the influence anddampens oscillations on the feedbacksignal from the control.This is an advantage if there is a lot ofnoise in the system.3.7.6 5-6* Pulse OutputsParameters for configuring the scaling and outputfunctions of pulse outputs. The pulse outputs aredesignated to terminal 27 or 29. Select terminal 27 outputin parameter 5-01 Terminal 27 Mode and terminal 29 outputin parameter 5-02 Terminal 29 Mode.Output valueOutput(Hz)High outputvalueP 5-60(term27)P 5-63(term29)High freq.P 5-62(term27)P 5-65(term29)130BA089.11Illustration 3.32 Pulse Output5-60 Terminal 27 Pulse Output VariableRange: Function:NOTICEThis parameter cannot beadjusted while the motor isrunning.[0] * No operation Select the operation variable assignedfor terminal 27 readouts.[45] Bus ctrl.[48] Bus ctrl., timeout[51] MCO controlled[100] Output frequency[101] Reference[102] Feedback[103] Motor current[104] Torque rel to limit[105] Torq relate to rated[106] Power[107] SpeedParameter Description Programming GuideMG20OB02 Danfoss A/S © 05/2018 All rights reserved. 873 3