16-36 Inv. Nom. CurrentRange: Function:Sizerelated*[0.01 -10000 A]View the inverter nominal current,which should match the nameplatedata on the connected motor. Thedata is used for calculation of torque,motor overload protection, and so on.16-37 Inv. Max. CurrentRange: Function:Sizerelated*[0.01 -10000 A]View the inverter maximum current,which should match the nameplatedata on the connected motor. Thedata is used for calculation of torque,motor overload protection, and so on.16-38 SL Controller StateRange: Function:0* [0 - 100 ] View the state of the event under execution bythe SL controller.16-39 Control Card Temp.Range: Function:0 °C* [0 - 100 °C] View the temperature on the control card,stated in °C.16-40 Logging Buffer FullOption: Function:View whether the logging buffer is full (seechapter 3.14.2 15-1* Data Log Settings). The loggingbuffer is never full when parameter 15-13 LoggingMode is set to [0] Log always.[0] * No[1] Yes16-42 Service Log CounterRange: Function:0* [ 0 -24 ]Shows the number of service logs stored in theServiceLog file. If the ServiceLog file is full, clear thelogged data by selecting option [5] Clear service logsin parameter 14-22 Operation Mode. The logged datais deleted on the next power-up.16-49 Current Fault SourceRange: Function:0* [0 - 8 ] The value indicates source of current fault,including:• Short circuit.• Overcurrent.• Imbalance of supply voltage (from left):1–4 – inverter, 5–8 – rectifier, 0 – no faultrecorded.After a short circuit alarm (Imax2), or overcurrent alarm(Imax1), or imbalance of supply voltage, this contains thepower card number associated with the alarm. It onlyholds 1 number indicating the highest priority power cardnumber (master first). The value persists on power cycle,but if a new alarm occurs it is overwritten by the newpower card number (even if it is a lower priority number).The value is only cleared when the alarm log is cleared(that is a 3-finger reset would reset the readout to 0).3.15.4 16-5* Ref. & Feedb.16-50 External ReferenceRange: Function:0* [-200 - 200 ] View the total reference, the sum of digital,analog, preset, fieldbus, and freeze references,plus catch up and slow down.16-52 Feedback[Unit]Range: Function:0ProcessCtrlUnit*[-999999.999- 999999.999ProcessCtrlUnit]View value of resulting feedbackvalue after processing of feedback1-3, see:• Parameter 16-54 Feedback1 [Unit].• Parameter 16-55 Feedback2 [Unit].• Parameter 16-56 Feedback3 [Unit].in the feedback manager.See parameter group 20-0*Feedback.The value is limited by settings inparameter 3-02 Minimum Referenceand parameter 3-03 MaximumReference. Units as set inparameter 20-12 Reference/Feedback Unit.16-53 Digi Pot ReferenceRange: Function:0* [-200 - 200 ] View the contribution of the digital potenti-ometer to the actual reference.16-54 Feedback 1 [Unit]Range: Function:0 ProcessCtrlUnit* [-999999.999 -999999.999ProcessCtrlUnit]View value offeedback 1, seeparameter group 20-0*Feedback.Parameter Description Programming GuideMG20OB02 Danfoss A/S © 05/2018 All rights reserved. 1513 3