10-11 Process Data Config WriteOption: Function:[411] Motor Speed Low Limit [RPM][412] Motor Speed Low Limit [Hz][413] Motor Speed High Limit [RPM][414] Motor Speed High Limit [Hz][416] Torque Limit Motor Mode[417] Torque Limit Generator Mode[553] Term. 29 High Ref./Feedb. Value[558] Term. 33 High Ref./Feedb. Value[590] Digital & Relay Bus Control[593] Pulse Out #27 Bus Control[595] Pulse Out #29 Bus Control[597] Pulse Out #X30/6 Bus Control[615] Terminal 53 High Ref./Feedb. Value[625] Terminal 54 High Ref./Feedb. Value[653] Terminal 42 Output Bus Control[663] Terminal X30/8 Output Bus Control[673] Terminal X45/1 Bus Control[683] Terminal X45/3 Bus Control[894] Bus Feedback 1[895] Bus Feedback 2[896] Bus Feedback 3[1680] Fieldbus CTW 1[1682] Fieldbus REF 1[1685] FC Port CTW 1[1686] FC Port REF 110-12 Process Data Config ReadOption: Function:Select the process read data for I/O assembly instances101/151. Elements 2 and 3 of this array can be selected.Elements 0 and 1 of the array are fixed.10-13 Warning ParameterRange: Function:0* [0 - 65535 ] View a DeviceNet-specific warning word. Onebit is assigned to every warning. Refer to theVLT® MCA 104 DeviceNet Installation Guide forfurther information.Bit Description0 Bus not active.1 Explicit connection timeout.2 I/O connection.3 Retry limit reached.4 Actual is not updated.5 CAN bus off.6 I/O send error.7 Initialization error.8 No bus supply.9 Bus off.10 Error passive.11 Error warning.Bit Description12 Duplicate MAC ID error.13 RX queue overrun.14 TX queue overrun.15 CAN overrun.Table 3.20 Warning Bits10-14 Net ReferenceRead only from LCP.Option: Function:Select the reference source in instances 21/71 and20/70.[0] * Off Enables reference via analog/digital inputs.[1] On Enables reference via the fieldbus.10-15 Net ControlRead only from LCP.Option: Function:Select the control source in instances 21/71 and 20/70.[0] * Off Enables control via analog/digital inputs.[1] On Enable control via the fieldbus.3.11.3 10-2* COS Filters10-20 COS Filter 1Range: Function:0* [0 -65535 ]Enter the value for COS filter 1 to set up thefilter mask for the status word. When operatingin COS (change-of-state), this function filtersout bits in the status word that should not besent if they change.10-21 COS Filter 2Range: Function:0* [0 -65535 ]Enter the value for COS filter 2 to set up thefilter mask for the Main Actual Value. Whenoperating in COS, this function filters out bits inthe main actual value that should not be sent ifthey change.10-22 COS Filter 3Range: Function:0* [0 - 65535 ] Enter the value for COS filter 3 to set up thefilter mask for PCD 3. When operating in COS,this function filters out bits in PCD 3 thatshould not be sent if they change.Parameter Description Programming GuideMG20OB02 Danfoss A/S © 05/2018 All rights reserved. 1113 3