16-55 Feedback 2 [Unit]Range: Function:0ProcessCtrlUnit*[-999999.999 -999999.999ProcessCtrlUnit]View value of feedback 2, seeparameter group 20-0*Feedback.The unit is set inparameter 20-12 Reference/Feedback Unit.16-56 Feedback 3 [Unit]Range: Function:0 ProcessCtrlUnit* [-999999.999 -999999.999ProcessCtrlUnit]View value offeedback 3, seeparameter group 20-0*Feedback.16-58 PID Output [%]Range: Function:0 %* [0 - 100 %] This parameter returns the frequencyconverter closed-loop PID controller outputvalue in percent.16-59 Adjusted SetpointRange: Function:0 ProcessCtrlUnit* [-999999.999 -999999.999ProcessCtrlUnit]Shows the value ofthe adjustedsetpoint.3.15.5 16-6* Inputs and Outputs16-60 Digital InputRange: Function:0N/A*[0 -1023N/A]View the signal states from the active digitalinputs. For example, input 18 corresponds to bit5. 0=No signal, 1=connected signal.Bit 0 Digital input terminal 33.Bit 1 Digital input terminal 32.Bit 2 Digital input terminal 29.Bit 3 Digital input terminal 27.Bit 4 Digital input terminal 19.Bit 5 Digital input terminal 18.Bit 6 Digital input terminal 37.Bit 7 Digital input GP I/O terminalX30/4.Bit 8 Digital input GP I/O terminalX30/3.Bit 9 Digital input GP I/O terminalX30/2.Bits 10–63 Reserved for future terminals.Table 3.26 Digital Input Bits16-61 Terminal 53 Switch SettingOption: Function:View the setting of input terminal 53.[0] * Current[1] Voltage16-62 Analog Input 53Range: Function:0* [-20 - 20 ] View the actual value at input 53.16-63 Terminal 54 Switch SettingView the setting of input terminal 54.Option: Function:[0] * Current[1] Voltage16-64 Analog Input 54Range: Function:0* [-20 - 20 ] View the actual value at input 54.16-65 Analog Output 42 [mA]Range: Function:0* [0 - 30 ] View the actual value at output 42 in mA. Thevalue shown reflects the selection inparameter 6-50 Terminal 42 Output.16-66 Digital Output [bin]Range: Function:0* [0 - 15 ] View the binary value of all digital outputs.16-67 Freq. Input #29 [Hz]Range: Function:0 N/A* [0 - 130000 N/A] View the actual frequency rate onterminal 29.16-68 Freq. Input #33 [Hz]Range: Function:0 N/A* [0 - 130000 N/A] View the actual frequency rate onterminal 33.16-69 Pulse Output #27 [Hz]Range: Function:0 N/A* [0 - 40000 N/A] View the actual value on terminal 27 indigital output mode.16-70 Pulse Output #29 [Hz]Range: Function:0 N/A* [0 - 40000 N/A] View the actual value of pulses onterminal 29 in digital output mode.Parameter Description VLT® AQUA Drive FC 202152 Danfoss A/S © 05/2018 All rights reserved. MG20OB0233