8-04 Control Timeout FunctionSelect the timeout function. The timeout function is activatedwhen the control word fails to be updated within the timeperiod specified in parameter 8-03 Control Timeout Time. [20] N2Override Release only appears after setting the Metasys N2protocol.To change the set-up after a timeout, configure as follows:1. Set parameter 0-10 Active Set-up to [9] Multi set-up.2. Select the relevant link in parameter 0-12 This Set-upLinked to.Option: Function:[7] Select setup 1 Changes the set-up after a controlword timeout. If communicationresumes after a timeout,parameter 8-05 End-of-TimeoutFunction either resumes the set-upused before the timeout, or retainsthe set-up endorsed by thetimeout function.[8] Select setup 2 See [7] Select set-up 1.[9] Select setup 3 See [7] Select set-up 1.[10] Select setup 4 See [7] Select set-up 1.[20] N2 OverrideRelease[27] Forced stop andtrip8-05 End-of-Timeout FunctionSelect the action after receiving a valid control word following atimeout.This parameter is active only when parameter 8-04 ControlTimeout Function is set to:• [7] Set-up 1.• [8] Set-up 2.• [9] Set-up 3.• [10] Set-up 4.Option: Function:[0] Hold set-up Retains the set-up selected inparameter 8-04 Control TimeoutFunction and shows a warning untilparameter 8-06 Reset Control Timeouttoggles. Then the frequencyconverter resumes its original set-up.[1] * Resume set-up Resumes the set-up that was activebefore the timeout.8-06 Reset Control TimeoutThis parameter is active only when option [0] Hold set-up hasbeen selected in parameter 8-05 End-of-Timeout Function.Option: Function:8-06 Reset Control TimeoutThis parameter is active only when option [0] Hold set-up hasbeen selected in parameter 8-05 End-of-Timeout Function.Option: Function:[0] * Do not reset Retains the set-up specified inparameter 8-04 Control Timeout Function:• [7] Set-up 1.• [8] Set-up 2.• [9] Set-up 3.• [10] Set-up 4.[1] Do reset Restores the frequency converter to theoriginal set-up following a control wordtimeout. The frequency converter performsthe reset and immediately reverts to the [0]Do not reset setting.8-07 Diagnosis TriggerNot all fieldbusses support the diagnosis functions.Option: Function:[0] * Disable Send no extended diagnosis data(EDD).[1] Trigger on alarms Send EDD after alarms.[2] Trigger alarm/warn. Send EDD after alarms or warnings.8-08 Readout FilteringIf the speed feedback value readouts on fieldbus are fluctuating,this function is used. Select filtered, if the function is required. Apower cycle is required for changes to take effect.Option: Function:[0] Motor DataStd-Filt.Normal fieldbus readouts.[1] Motor Data LP-FilterFiltered fieldbus readouts of the followingparameters:• Parameter 16-10 Power [kW].• Parameter 16-11 Power [hp].• Parameter 16-12 Motor Voltage.• Parameter 16-14 Motor Current.• Parameter 16-16 Torque [Nm].• Parameter 16-17 Speed [RPM].• Parameter 16-22 Torque [%].Parameter Description Programming GuideMG20OB02 Danfoss A/S © 05/2018 All rights reserved. 1013 3