3.9.2 8-1* Ctrl. Word Settings8-10 Control ProfileSelect the interpretation of the control and status wordscorresponding to the installed fieldbus. Only the selections validfor the fieldbus installed in slot A are visible in the LPC display.For guidelines in selection of [0] Frequency converter profile and[1] PROFIdrive profile, refer to the design guide of the relatedproduct. For more guidelines in the selection of [1] PROFIdriveprofile, [5] ODVA, and [7] CANopen DSP 402, see the installationguide for the installed fieldbus.Option: Function:[0] * FC profile[1] PROFIdrive profile[5] ODVA Available only with VLT®DeviceNet MCA 104 andVLT® EtherNet/IP MCA121.[7] CANopen DSP 4028-13 Configurable Status Word STWThis parameter enables configuration of bits 12–15 in the statusword.Array [16]Option: Function:[0] No function[1] * Profile Default The function corresponds to the profiledefault selected in parameter 8-10 ControlProfile.[2] Alarm 68 Only Only set if alarm 68, Safe Torque Offoccurs.[3] Trip excl Alarm68Set if a trip occurs, unless alarm 68, SafeTorque Off is set to execute the trip.[10] T18 DI status The bit indicates the status of terminal18.0 indicates that the terminal is low.1 indicates that the terminal is high.[11] T19 DI status The bit indicates the status of terminal19.0 indicates that the terminal is low.1 indicates that the terminal is high.[12] T27 DI status The bit indicates the status of terminal27.0 indicates that the terminal is low.1 indicates that the terminal is high.[13] T29 DI status The bit indicates the status of terminal29.0 indicates that the terminal is low.1 indicates that the terminal is high.[14] T32 DI status The bit indicates the status of terminal32.0 indicates that the terminal is low.8-13 Configurable Status Word STWThis parameter enables configuration of bits 12–15 in the statusword.Array [16]Option: Function:1 indicates that the terminal is high.[15] T33 DI status The bit indicates the status of terminal33.0 indicates that the terminal is low.1 indicates that the terminal is high.[16] T37 DI status The bit indicates the status of terminal37.0 indicates that T37 is low (Safe TorqueOff).1 indicates that T37 is high (normal).[20] CTW TimeoutToggle Inverse[21] ThermalwarningThe thermal warning turns on when thetemperature exceeds the limit in themotor, frequency converter, brakeresistor, or thermistor.[30] Brake fault(IGBT)Output is logic 1 when the brake IGBT isshort-circuited. Use this function toprotect the frequency converter if thereis a fault on the brake modules. Use theoutput/relay to cut out the main voltagefrom the frequency converter.[40] Out of ref range[60] Comparator 0 See parameter group 13-1* Comparators. Ifcomparator 0 is evaluated as true, theoutput goes high. Otherwise, it is low.[61] Comparator 1 See parameter group 13-1* Comparators. Ifcomparator 1 is evaluated as true, theoutput goes high. Otherwise, it is low.[62] Comparator 2 See parameter group 13-1* Comparators. Ifcomparator 2 is evaluated as true, theoutput goes high. Otherwise, it is low.[63] Comparator 3 See parameter group 13-1* Comparators. Ifcomparator 3 is evaluated as true, theoutput goes high. Otherwise, it is low.[64] Comparator 4 See parameter group 13-1* Comparators. Ifcomparator 4 is evaluated as true, theoutput goes high. Otherwise, it is low.[65] Comparator 5 See parameter group 13-1* Comparators. Ifcomparator 5 is evaluated as true, theoutput goes high. Otherwise, it is low.[70] Logic Rule 0 See parameter group 13-4* Logic Rules. Iflogic rule 0 is evaluated as true, theoutput goes high. Otherwise, it is low.[71] Logic Rule 1 See parameter group 13-4* Logic Rules. Iflogic rule 1 is evaluated as true, theoutput goes high. Otherwise, it is low.Parameter Description VLT® AQUA Drive FC 202102 Danfoss A/S © 05/2018 All rights reserved. MG20OB0233