2.2.2 Quick Transfer of Parameter Settingsbetween Multiple FrequencyConvertersOnce the set-up of a frequency converter is complete,store the data in the LCP or on a PC via MCT 10 Set-upSoftware.Autoon ResetHandon OffStatus QuickMenuMainMenuAlarmLogBackCancelInfoOKOnAlarmWarn.130BA027.10Illustration 2.10 LCPData storage in LCPNOTICEStop the motor before performing this operation.To store the data in the LCP:1. Go to parameter 0-50 LCP Copy.2. Press the [OK] key.3. Select [1] All to LCP.4. Press the [OK] key.All parameter settings are now stored in the LCP indicatedby the progress bar. When 100% is reached, press [OK].Connect the LCP to another frequency converter and copythe parameter settings to this frequency converter as well.Data transfer from LCP to frequency converterNOTICEStop the motor before performing this operation.To transfer the data from the LCP to the frequencyconverter:1. Go to parameter 0-50 LCP Copy.2. Press the [OK] key.3. Select [2] All from LCP.4. Press the [OK] key.The parameter settings stored in the LCP are nowtransferred to the frequency converter indicated by theprogress bar. When 100% is reached, press [OK].2.2.3 Display ModeIn normal operation, up to 5 different operating variablescan be indicated continuously in the middle section: 1.1,1.2, and 1.3, as well as 2 and 3.2.2.4 Display Mode - Selection of ReadoutsPress [Status] to toggle between 3 status readout screens.Operating variables with different formatting are shown ineach status screen. For more information, see the examplesin this chapter.Several values or measurements can be linked to each ofthe shown operating variables. The values ormeasurements to be shown can be defined via thefollowing parameters:• Parameter 0-20 Display Line 1.1 Small.• Parameter 0-21 Display Line 1.2 Small.• Parameter 0-22 Display Line 1.3 Small.• Parameter 0-23 Display Line 2 Large.• Parameter 0-24 Display Line 3 Large.Access the parameters via [Quick Menu], Q3 Function Set-ups, Q3-1 General Settings, Q3-13 Display Settings.Each readout parameter selected in parameter 0-20 DisplayLine 1.1 Small to parameter 0-24 Display Line 3 Large has itsown scale and digits after a decimal point. The highernumeric value of a parameter, the fewer digits are shownafter the decimal point.Example: Current readout 5.25 A; 15.2 A; 105 A.See parameter group 0-2* LCP Display for further details.How to Program Programming GuideMG20OB02 Danfoss A/S © 05/2018 All rights reserved. 172 2