3.15 Parameters 16-** Data Readouts3.15.1 16-0* General Status16-00 Control WordRange: Function:0* [0 - 65535 ] View the control word sent from the frequencyconverter via the serial communication port inhex code.16-01 Reference [Unit]Range: Function:0 ReferenceFeed-backUnit*[-999999 -999999ReferenceFeed-backUnit]View the present referencevalue applied on impulse oranalog basis in the unitresulting from the configu-ration selected inparameter 1-00 Configu-ration Mode (Hz, Nm, orRPM).16-02 Reference [%]Range: Function:0 %* [-200 -200 %]View the total reference. The total referenceis the sum of digital, analog, preset, bus,and freeze references, plus catch up andslow down.16-03 Status WordRange: Function:0* [0 - 65535 ] View the status word sent from the frequencyconverter via the serial communication port inhex code.16-05 Main Actual Value [%]Range: Function:0.00 %* [-100.00 -100.00 %]View the 2 byte word sent with thestatus word to the fieldbus masterreporting the main actual value. Refer tothe VLT® PROFIBUS DP MCA 101Programming Guide for further details.16-09 Custom ReadoutRange: Function:0 CustomRea-doutUnit*[-999999.99 -999999.99CustomRea-doutUnit]View the user-defined readoutsas defined inparameter 0-30 Custom ReadoutUnit, parameter 0-31 CustomReadout Min Value, andparameter 0-32 Custom ReadoutMax Value.3.15.2 16-1* Motor Status16-10 Power [kW]Range: Function:0 kW* [0 -10000kW]Shows motor power in kW. The value shownis calculated based on the actual motorvoltage and motor current. The value isfiltered, and therefore approximately 1.3 smay pass from when an input value changesto when the data readout values change. Theresolution of readout value on fieldbus is in10 W steps.16-11 Power [hp]Range: Function:0 hp* [0 -10000 hp]View the motor power in hp. The valueshown is calculated based on the actualmotor voltage and motor current. The valueis filtered, and therefore approximately 1.3 msmay pass from when an input value changesto when the data readout values change.16-12 Motor VoltageRange: Function:0 V* [0 - 6000 V] View the motor voltage, a calculated valueused for controlling the motor.16-13 FrequencyRange: Function:0 Hz* [0 - 6500 Hz] View the motor frequency withoutresonance damping.16-14 Motor currentRange: Function:0 A* [0 - 10000A]View the motor current measured as anaverage value, IRMS. The value is filtered, andthus approximately 1.3 s may pass fromwhen an input value changes to when thedata readout values change.16-15 Frequency [%]Range: Function:0 %* [-100 -100 %]View a 2-byte word reporting the actual motorfrequency (without resonance damping) as apercentage (scale 0000–4000 hex) ofparameter 4-19 Max Output Frequency. Setparameter 9-16 PCD Read Configuration index 1to send it with the status word instead of theMAV.Parameter Description Programming GuideMG20OB02 Danfoss A/S © 05/2018 All rights reserved. 1493 3