Chapter 5—System Configuration and OperationPower Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com 93Control SettingsThe following parameters are used to configure the Two SpeedDahlander Operation Mode and the C445 sources of control.Table 19. Two Speed Dahlander Configuration ParametersNote1 Soft reset (power cycle) required for changes to these parameters to take effect.Fieldbus Control WordThe two speed Dahlander motor starter profile will acceptthe following control commands over a fieldbus network.Control BitsBit 0/1 00 = Stop command, de-activate all control outputs01 = Run Slow command, activate Output 110 = Run Fast command, activate Outputs 2 & 311 = Unknown command, No actionBit 3 0 = No action1= Reset fault (will clear fault provided conditionhas cleared)Bit 5 0 = No action1= The C445 will issue a “Test Trip” fault causingthe Outputs 1-3 control relays to open.Control Status WordThe control status word of the two speed Dahlander motorstarter profile can be accessed over the fieldbus network.Status BitsBit 0/1 00 = Stopped (No active Run commands)01= Running1 (Run Slow command is active)10= Running2 (Run Fast command is active)Bit 2 0 = local control source active1= remote control source is activeBit 3 0 = no fault present1= C445 fault presentBit 4 0 = no warning present1= C445 warning presentBit 5 0 = no inhibit present1= C445 control inhibit presentBit 6 0 = C445 not ready (fault and/or inhibit present)1= C445 ready for control (No fault or inhibit present)Bit 7 0 = motor is not up to speed (AtRef)1= C445 has detected motor is up to speed (AtRef)Two conditions will set the AtRef bit, signaling the motor isup to speed.● If motor current first exceeds 115% of the active overloadFLA rating and then decreases back below 115% of theactive overload FLA rating, it is determined the motor hascome up to speed and the AtRef bit will be set.● If motor current exceeds 30% of the active overload FLArating and remains until after the start delay time expiresthe motor is determined to be up to speed and the AtRefbit will be set.Configuration Parameter Modbus Register Description Read/WriteActive Operation Mode 1 700 This parameter selects the Operation Mode R/WControl Fault Delay 701 Delay time before a control fault is issued. Setting of “0” disables protection. R/WControl Switch Time Delay 703 Time delay when transitioning from fast R slow. Delay to allow motor to slow beforetransitioning to the slow output (in 10ms)R/WNetwork Contactor Settle Time 704 Settle delay time before 2 nd contactor is activated – ensures the net contactor issealed in before activating the fast output (in 10ms)R/WMotor#1 Overload FLA Scaled 900 Parameter to set overload full load amps for slow motor winding R/WMotor#2 Overload FLA Scaled 901 Parameter to set overload full load amps for fast motor winding R/WMotor Overload Trip FLA 500 This parameter contains the active motor overload FLA rating(will contain the motor1 setting when on the slow winding and the motor2 settingwhen on the fast winding)RTrip Enable Bit Field 1000-1001 Trip (Fault) protection enable bitsSet bits to enable desired motor protectionsR/WWarn Enable Bit Field 1002-1003 Warning protection enable bitsSet bits to enable desired motor protections warningsR/WC445 Local Source Selector 1 711 Select the Local Control source. R/WC445 Remote Source Selector 712 Select the Remote Control source. R/W