Appendix C—Optional Communication Cards222 Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.comInstance AttributesSr. No. ID Description Access Rule Data Type Remarks1 1 (0x1) Status Get DWORD 01 00 00 002 2 (0x2) Configuration Capability Get DWORD F4 00 00 003 3 (0x3) Configuration Control Get / Set DWORD 02-dhcp, 0- static4 4 (0x4) Physical Link Get STRUCT ofPath Size UINT 0Path Padded EPATH 05 5 (0x5) Interface Configuration Get / Set Struct of:-NVIP Address UDINT 192.168.1.254Network Mask UDINT 255.255.255.0Gateway Address UDINT 192.168.1.1Name Server UDINT 0Name Server 2 UDINT 0Domain Name STRING 06 6 (0x6) Host Name Get / Set STRING 07 8 (0x8) TTL Value Get USINT 18 9 (0x9) Multicast Configuration Get Struct of:Alloc Control USINT 0Reserved USINT 0Number of Mcast UINT 0x20Starting Multicast Address DWORD 80 20 C0 EE9 10 (0xA) SelectAcd Set / Get BOOL 110 11 (0xB) Last Conflict Detected Set / Get Struct of:ACD activity USINT 0Remote MAC Array of 6 USINT 0ARP PDU Array of28 USINT 011 13 (0xD) Encapsulation Inactivity Timeout Set / Get UINT 0 = Disable1-3600 = timeout in secondsDefault = 120Table 115. Ethernet Link Object—Class 0xF6 (246)Class ServicesServiceCode Service Name0x0E Get Attribute Single0x01 Get Attributes AllInstance ServicesServiceCode Service Name0x0E Get Attribute Single0x10 Set Attribute Single0x01 Get Attributes AllTable 114. TCP/IP Object—Class 0xF5 (245), continued