Appendix C—Optional Communication CardsPower Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com 183Output Instance 2: Basic OverloadLength = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Reserved Reserved Reserved FaultReset Reserved ReservedOutput Instance 3: Basic Motor StarterLength = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Reserved Reserved Reserved FaultReset Reserved Run1Output Instance 5: Extended Motor StarterLength = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Reserved Reserved Reserved FaultReset Run2 Run1Input Instance 50: Basic OverloadLength = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Fault/TripInput Instance 51: Extended OverloadLength = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Reserved Reserved Reserved Reserved Warning Fault/tripInput Instance 52: Basic Motor StarterLength = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Reserved Reserved Reserved Running 1 Reserved Faulted/TrippedInput Instance 54: Extended Motor Starter 2Length = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Cntr lfrom Net Ready Running 2 Running 1 Warning Faulted/Trip