Appendix C—Optional Communication Cards212 Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.comInstance AttributesSr. No. Attribute ID Access Data Type Attribute Name Attribute Description1 1 (0x1) Get/Set BYTE Trip Enable Bit Field Enabling bits for tripping.Bit location - condition0 - under voltage1 - over voltage2 - high resistance GF3 - residual GF4 - current phase loss5 - current unbalance6 - instantaneous over current7 - jam8 - PF deviation9 - voltage phase loss10 - voltage unbalance11 - freq deviation fast12 - freq deviation slow13 - under current14 - high power15 - low power16 - overload17 - stall18 - phase rotation19 - exceeds starts limit20 - PTC21 - initialization fault22 - NV memory fault23 - comm loss24 - comm msg error2 2 (0x2) Get/Set BYTE Warn Enable Bit Field Enabling bits for warning.Bit location - condition0 - under voltage1 - over voltage2 - high resistance GF3 - residual GF4 - current phase loss5 - current unbalance6 - instantaneous over current7 - jam8 - PF deviation9 - voltage phase loss10 - voltage unbalance11 - freq deviation fast12 - freq deviation slow13 - under current14 - high power15 - low power16 - overload17 - stall18 - phase rotation19 - exceeds starts limit20 - PTC21 - initialization fault22 - NV memory fault23 - comm loss24 - comm msg error3 3 (0x3) Get/Set UINT Alarm Debounce Time Alarm Debounce Time4 4 (0x4) Get/Set BOOL Global Auto Reset Enable (Boolean) If disabled, no auto reset; if enabled, auto reset based ontrip auto-reset bitsTable 106. Motor Protection Object—Class 0xA2 (162), continued