Appendix D—Modbus Register MapPower Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com 2997002 Overlay type UINT8 RODefault: 255EnumThe Overlay type for the User Interface - Applies to C445UC… modelsonly.Write-protected by manufacturing lock service. Preserved on WipeNV.7003 Base Control ModuleProduct NameSTRING8 ROArray size: 32Base Control Module Product Name, short description of the ProductCodeArray of 16 registers7025 Base Control ModuleAssigned NameSTRING8 RW NVArray size: 32Default: “Power XpertC445”Config CRCAdmin LockUSB LockBackup MemBase Control Module User Assigned Name. The default is “Power XpertC445”, but optionally may be changed.Array of 16 registers7041 Base Control Module SerialNumberUINT32 RO Base Control Module Serial Number (32 bit format).Write-protected by manufacturing lock service. Preserved on WipeNV.7043 Base Control ModuleProduct CodeUINT16 RO Base Control Module Product Code (numerical format)7044 Base Control ModuleProduct Sub CodeUINT16 RO Base Control Module Product Sub CodeWrite-protected by manufacturing lock service. Preserved on WipeNV.7045 Base Control ModuleFirmware VersionUINT16 ROArray size: 2Base Control Module Firmware VersionArray of 2 registersTable 127. C445 Modbus Register Map, continuedRegister Name Attribute DescriptionValue Description0 No predefined User Interface overlay selected1 30-46625-101 IEC User Interface Overlay2 30-46625-102 IEC User Interface Overlay3 30-46625-103 IEC User Interface Overlay4 30-46625-104 IEC User Interface Overlay5 30-46625-105 IEC User Interface Overlay6 30-46625-106 IEC User Interface Overlay7 30-46625-107 IEC User Interface Overlay8 30-46625-108 IEC User Interface Overlay9 30-46625-109 IEC User Interface Overlay10 30-46625-110 IEC User Interface Overlay11 30-46625-201 NEMA User Interface Overlay12 30-46625-202 NEMA User Interface Overlay13 30-46625-203 NEMA User Interface Overlay14 30-46625-204 NEMA User Interface Overlay15 30-46625-205 NEMA User Interface Overlay16 30-46625-206 NEMA User Interface Overlay17 30-46625-207 NEMA User Interface Overlay18 30-46625-208 NEMA User Interface Overlay19 30-46625-209 NEMA User Interface Overlay20 30-46625-210 NEMA User Interface Overlay21 MUI connected255 Out of box or factory reset state. No User Interface wasever connected