Appendix D—Modbus Register MapPower Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com 2811047 High Power Alarm Level SINT16 RW NVDefault: 110Range: -200 to 200Units: %Config CRCAdmin LockUSB LockBackup MemHigh Power Alarm Level (based on KW) when exceeded and following theAlarm Delay Time in the Protections/General category, will generate awarning.1048 High Power Trip Delay UINT16 RW NVDefault: 20Range: 1 to 60Units: secondsConfig CRCAdmin LockUSB LockBackup MemHigh Power Trip Delay is the time delay following the trip level beingexceeded until a trip occurs.1049 Low Power Trip Level SINT16 RW NVDefault: 50Range: -200 to 200Units: %Config CRCAdmin LockUSB LockBackup MemLow Power Trip Level will trip the motor if the calculated KW Level dropsbelow this threshold, following the Low Power Trip Delay time.1050 Low Power Alarm Level SINT16 RW NVDefault: 50Range: -200 to 200Units: %Config CRCAdmin LockUSB LockBackup MemLow Power Alarm Level when exceeded and following the Alarm DelayTime in the Protections/General category, will generate a warning.1051 Low Power Trip Delay UINT16 RW NVDefault: 20Range: 1 to 60Units: secondsConfig CRCAdmin LockUSB LockBackup MemLow Power Trip Delay is the time delay following the trip level beingexceeded until a trip occurs.1052 Peak Demand WarningThresholdUINT32 RW NVDefault: 0Units: WConfig CRCAdmin LockUSB LockBackup MemGenerate an alarm if the peak demand exceeds this threshold.1054 Demand Window Duration UINT16 RW NVDefault: 15Range: 1 to 240Units: minutesConfig CRCAdmin LockUSB LockBackup MemThe duration over which the Demand is measured. In North America thisduration is usually chosen to be 15 minutes.Table 127. C445 Modbus Register Map, continuedRegister Name Attribute Description