Appendix C—Optional Communication CardsPower Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com 201Instance AttributesSr. No. ID Access Rule Data Type Description22 111 (0x6F) Get USINT Config InhibitReason0: No active inhibits1: Local and Remote motor control sources both point toFieldwire2: Local motor control source is set to User Interface but theUser Interface type does not match3: One or more enabled protection features requires avoltage option card in the Measurement Module4: One or more enabled protection features requires a PTC(Temperature) option card in the Measurement Module5: Selected starter profile is incompatible with fieldwire aslocal control or fieldwire type6: Cannot choose fieldwire as the feedback source when thefieldwire is used as a local / remote source with the selectedstarter7: UI Custom Overlay - Multiple buttons assigned to samefunction8: UI Custom Overlay - Multiple functions assigned to thesame button LED9: UI Custom Overlay - Multiple functions assigned to thesame status LED10: Selected starter profile is incompatible with theconnected UI11: The General Purpose I/O operational mode does not usefieldwire as a control source23 112 (0x70) Get/Set USINT Motor ControlCommunicationLoss Behavior0: Stop on comloss event - no fault1: Ignore comloss and keep present state2: Send RUN1 command on comloss event3: Send RUN2 command on comloss event4: Stop C445 controller and issue comloss fault424 113 (0x71) Get/Set USINT Motor ControlNetwork IdleBehavior0: Stop on idle event1: Ignore idle and keep present state2: Send RUN1 command on idle event3: Send RUN2 command on idle event025 114 (0x72) Get/Set USINT System Services 0: No Active Service1: Clear fault queue2: Clear trip snapshot3: Test trip4: Re-pair external modules5: Factory reset6: Soft reset7: Reset Fault8: Proof Test26 115 (0x73) Get USINT Proof TestStatus0: Proof Test was never run after a power cycle1: Proof Test currently running2: Proof Test passed3: Proof Test failed027 116 (0x74) Get UINT Base ControlModule FaultQueue - 1A list of faults based on most recent. Duplicates are notallowed. They are sorted by event with the newest at the topof the queue.28 117 (0x75) Get UINT Base ControlModule FaultQueue - 2A list of faults based on most recent. Duplicates are notallowed. They are sorted by event with the newest at the topof the queue.29 118 (0x76) Get UINT Base ControlModule FaultQueue – 3A list of faults based on most recent. Duplicates are notallowed. They are sorted by event with the newest at the topof the queue.Table 96. Control Supervisor Object—Class 0x29 (41), continued