Appendix C—Optional Communication CardsPower Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com 185Output Instance 105 (0x69): Basic Starter RelayLength = 2 BytesByteOffsetSize(bytes) Name Description0 2 Basic Overloadw/RelayBasic Overload with RelaysBit 0 = Output #1Bit 1 = Output #2Bit 2 = Output #3 (set)Bit 3 = Fault ResetBit 4 = Output #3 (reset)Bit 5 = Test TripBit 6 to 15 = reservedOutput Instance 106 (0x6A): Basic Output ControlLength = 2 BytesByteOffsetSize(bytes) Name Description0 2 Basic Control Relay Basic Control Bits:(Byte1: NETCTRL_CONTROL_WORD)(Byte2: BCM_FIELD_OUTPUTS)Bit 0: Run1Bit 1: Run2Bit 2: ReservedBit 3: Fault ResetBit 4: Enable Control From Network ProtocolBit 5: Test TripBit 6: ReservedBit 7: ReservedBit 8: Output #1 (Conditional. Depends on profile selected)Bit 9: Output #2 (Conditional. Depends on profile selected)Bit 10: Output #3 (set) (Conditional. Depends on profile selected)Bit 11: Output #3 (reset) (Conditional. Depends on profile selected)Bits 12–15: Reserved