Chapter 8—C445UM Monitoring User Interface158 Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.comC445UM MonitoringFive monitoring menus provide easy access to criticalsystem data.I: Current MonitoringV: Voltage MonitoringP: Power MonitoringT: Thermal MonitoringO: Other System MonitoringFigure 164. C445UM Monitoring MenusFigure 165. Monitoring Menu DataData inmenutoUsescrollMonitoring Menus: Press to toggle throughI (Current)Avg Current (Iavg)Iavg % of FLA (I%FLA)Current Unbalance (IUnb)Ground Fault Current (IGF)I Phase A (IA)I Phase B (IB)I Phase C (IC)V (Voltage)Avg Voltage(Vavg)Voltage Unbalance (VUnb)Phase Order (Ph Ord)Voltage L1-L2 (L1-L2)Voltage L2-L3 (L2-L3)Voltage L3-L1 (L3-L1)P (Power)Watts Total (P Watts)Power Factor (PF)VA Total (P VA)VARs Total (P VARS)Real Energy* (P kWh)T (Thermal)Thermal Memory % (TM%)Time to Reset (T to Rst)Thermal Capacity % (TC%)PTC state (PTC)O (Other)Run Time* (Run Time)# Motor Starts (#Starts)Max. Starting I (MaxStart)Last Start Time (LastStart)Frequency (Freq)RTC Time (RTC Time)IP Address (IP Addr)Operating Time* (Op Time)Contactor Ops Last Hr (Ctr Ops)Speed RPM (Speed)*Resettable parameter—Users can reset to zero in PRG menu.