Appendix D—Modbus Register MapPower Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com 235Appendix D—Modbus Register MapC445 Modbus Register MapTable 127. C445 Modbus Register MapRegister Name Attribute Description300 Motor Control Status BYTE ROBitfieldPresent Motor Control Status Bits (Running1, Running2, Remote, Tripped,Warned).301 I Phase A (L1) Scaled UINT16 ROUnits: scaled APhase A (L1) Motor Current Scaled. Scaled by parameter “I ScaleFactor”.302 I Phase B (L2) Scaled UINT16 ROUnits: scaled APhase B (L2) Motor Current Scaled. Scaled by parameter “I ScaleFactor”.303 I Phase C (L3) Scaled UINT16 ROUnits: scaled APhase C (L3) Motor Current Scaled. Scaled by parameter “I ScaleFactor”.304 Avg Current Scaled UINT16 ROUnits: scaled AAverage motor Current Scaled. Scaled by parameter “I Scale Factor”.305 I Scale Factor UINT16 RO This scale factor is applied to all current values monitored via acommunication network.306 Current Unbalance UINT8 ROUnits: %Motor Current Unbalance Percent307 GF Current RMS Scaled UINT16 ROUnits: scaled AMotor Residual Ground Fault scaled current RMS. Scaled by parameter “IScale Factor”.308 Thermal Capacity UINT8 RODefault: 0Units: %Thermal Capacity in Percent - An overload trip occurs when the ThermalCapacity reaches 100%.309 Time to Trip Overload UINT16 ROUnits: secondsEstimated Time for Overload to Reach Trip Threshold (100% ThermalMemory)310 Remaining ThermalCapacityUINT8 ROUnits: %Thermal Capacity (Percent) Remaining to Trip311 Time to Reset Overload UINT16 ROUnits: secondsTime for overload to reach reset threshold. The Thermal Memory mustdrop below 75% (default value) before a reset is allowed.Bit Description Coil0 Running 1 47851 Running 2 47862 Remote enabled 47873 Faulted 47884 Warning 47895 Inhibited 47906 Ready 47917 Motor at speed 4792